Hydrant Valves
DIN86211 Hydrant Valve
# Angle Pattern
Features:
- Bolted Bonnet Connection
- Manual Handwheel Operation
- Rotatable Valve Disc
- Replaceable Sealing
- ISO 10497-2010 Fire Test Approved
- Optional hydrant outlets including Storz、John Morris(Instantaneous) Nakajima、Machino or others by requesting
- Designed and manufactured according to DIN 86211
- Tested according to EN 12266-1-2012
- DNV Type Approval
Application:
- Applicable to Fire Fighting Systems : Both on-shore and off-shore
- Operating temperature : 0°C ~ 120°C
- Maximum Operating Pressure : 16 bar
- Medium can be seawater and fresh water
#Straight Pattern
Features:
- Bolted Bonnet Connection
- Manual Handwheel Operation
- Rotatable Valve Disc
- Replaceable Sealing
- ISO 10497-2010 Fire Test Approved
- Optional hydrant outlets including Storz、John Morris(Instantaneous) Nakajima、Machino or others by requesting
- Designed and manufactured according to DIN 86211
- Tested according to EN 12266-1-2012
- DNV Type Approval
Application:
- Applicable to Fire Fighting Systems : Both on-shore and off-shore
- Operating temperature : 0°C ~ 120°C
- Maximum Operating Pressure : 16 bar
- Medium can be seawater and fresh water
Marine Hydrant Valve
Features:
- Screwed Bonnet Connection
- Manual Handwheel Operation
- Rotatable Valve Disc
- Renewable Disc Sealing
- Tested according to EN 12266-1-2012
- Optional hydrant outlets including Storz、John Morris(Instantaneous) Nakajima、Machino or others by requesting
Application:
- Applicable to Fire Fighting Systems : Both on-shore and off-shore
- Operating temperature : 0°C ~ 80°C
- Maximum Operating Pressure : 16 bar
- Medium can be seawater and fresh water
DIN Landing Valve
Features:
- Screwed Bonnet Connection
- Manual Handwheel Operation
- Rotatable Valve Disc
- Replaceable Sealing
- Optional hydrant outlets including Storz、John Morris(Instantaneous) Nakajima、Machino or others by requesting
- Designed and manufactured according to DIN 14461-3
- Tested according to EN 12266-1-2012
Application:
- Applicable to Fire Fighting Systems : Delivery valve installation
- Operating temperature : 0°C ~ 38°C
- Maximum Operating Pressure : 16 bar
- Medium can be seawater and fresh water
JIS Hydrant Valve
Features:
- Screwed Bonnet Connection
- Manual Handwheel Operation
- Rotatable Valve Disc
- Renewable Disc Sealing
- Tested according to EN 12266-1-2012
Application:
- Applicable to Fire Fighting Hydrant Systems
- Operating temperature : 0°C ~ 80°C
- Maximum Operating Pressure : 10 / 16 bar
- Medium can be seawater and fresh water
BS5041 Landing Valve
Features:
- Screwed Bonnet Connection
- Manual Handwheel Operation
- Rotatable Valve Disc
- Renewable Disc Sealing
- Designed and constructed in accordance with BS 5041 standard
- Tested according to BS 5041 standard
Application:
- Applicable to Fire Fighting Systems : wet and dry rising main
- Operating temperature : 0°C ~ 38°C
- Maximum Operating Pressure : 15 bar
- Medium can be seawater and fresh water
- Suitable for both on-shore and off-shore application
Fire Hose Angle Valve
Features:
- Manufactured in accordance with UL 668
- FM Approval
- Polished or chrome plated parts with other outlet threads are also available
Application:
- Angle hose valves are designed for use with a fire hose rack assembly or as a fire department outlet connection
- Operating Pressure : 300 PSI
Pressure Reduce Valve
Features:
- Having a constant outlet pressure by oscillate inlet pressure
- Adjustable outlet pressure: 3 bar up to 10 bar
- Low friction lost design
- Compact and simple design
- Designed and constructed in accordance with BS 5041 standard
- Tested according to BS 5041 standard
Application:
- Suitable for firefighting system in high rise buildings and offshore industry
- Operating temperature : 0°C ~ 38°C
- Maximum Operating Pressure : 20 bar
- Medium can be seawater and fresh water
Brass Hydrant Gate Valve
Features:
- L shaped easy crank handle
- Pin lug swivel inlet
- Non-rising stem
- Metal to metal seat
Application:
- Used to throttle the flow from a fire hydrant preventing damage to the hydrant.
- Applicable to use on hydrants, standpipes, and fire pumps
- Operating temperature : 0°C ~ 38°C
- Maximum Operating Pressure : 175 psi
- Fresh water only